2ND CLASS POWER
ENGINEERING 2B2
PRACTICE EXAM
Question 1: In a single element feedwater control system, the variable used for
control is:
Choices:
1) Steam ow 2) Feedwater ow 3) Steam pressure 4) Drum level
Correct Answer: Drum level
Explanation: Single element uses only drum level.
Page 1
Question 2: Self operated single element feedwater systems such as
thermohydraulic systems typically:
Choices:
1) compensate for shrink and swell 2) maintain a reasonably narrow proportional band 3) close the feedwater valve on an initial increase in steaming rate 4) require an external source of power Correct Answer: close the feedwater valve on an initial increase in steaming rate Explanation: They react to the initial shrink/swell which can be opposite to required ow.Question 3: Hydrostatic head is:
Choices:
1) dependent upon the volume of liquid 2) independent of the shape of the vessel 3) based on the expansion of liquids 4) only expressed in terms of pressure
Correct Answer: independent of the shape of the vessel
Explanation: Hydrostatic head depends only on height and density, not vessel shape.Page 2
Question 4: A feedforward control strategy where a ratio between two process
variables is desired to be maintained at a specic set point is referred to as:
Choices:
1) Cascade control 2) Derivative control 3) Integral control 4) Ratio control
Correct Answer: Ratio control
Explanation: Ratio control maintains a set ratio between two variables.
Question 5: A proportional controller is implemented to eliminate the _______ of an on/o controller.
Choices:
1) derivative gain 2) reset time 3) cycling 4) oset
Correct Answer: cycling
Explanation: Proportional control smooths out the constant cycling of on/o control.Page 3